APPLICATION:
JD158LE-100 series leakage circuit breaker is suitable for AC 50/60Hz, rated voltage up to 230V/400V, rate

Detailed

APPLICATION:
JD158LE-100 series leakage circuit breaker is suitable for AC 50/60Hz, rated voltage up to 230V/400V, rated current 100A and below, used to protect person against indirect contact, and protect circuitry and equipment against overload or short-circuit. It also can be used to switch the circuitry or start the motor infrequently under normal condition.The products comply with GB14048.2-2001&IEC60947-2:1997MAIN TECHNICAL PARAMETERSBreak time of rated residual current operation
No. le(A) I?nm A Max break time(S) and min-driving time(S)
I?n 2 I?n 3 I?n 4 I?n
General type 6380 equal or greater than 30 0.1 0.06 0.04 0.04 Max break time
TimeDelaytype UltimateNon-driving time 0.06s0.1s greater than 30 0.4 0.2 0.15 0.15
0.13 0.06 0.05 0.04 Min non-driving time
100 0.6 0.4 0.3 0.2 Max break time
0.23 0.1 0.06 0.05 Min non-driving time
For I?n?30m A general type residual current operating circuit breaker,0.25A can be applied to replace 5I?n, 0.5A can be applied to replace 10I?n.

Over-current protection characteristics.
Rated Current(A) Initialstate Testcurrent Specified time Prospectiveresult Remark
le=63A le is greater than 63A
63A]80A100A Cold state 1.05le t is equal or greater than 1h t is equal or greater than 2h Non-trip
Proceed Following The previousTest item 1.30le t is less than 1h t is less than 2h Trip The current rises to the specified value steadilyWithin 5s
Cold state 8le t is equal or greater than 0.2s Non-trip Put through the powerSupply through closing the auxiliaryswitch
Cold state 12le t is less than 0.2s Trip Put through the powerSupply through closing the auxiliaryswitch