Follow us :

Contactor-2

Contactor-2
group name
Contactors
Min Order
1 piece
update time
Fri, 08 Jul 2011 17:07:32 GMT

Packging & Delivery

  • Min Order1 piece

Briefing

LC1-D series AC contactor is suitable for suing in the circuits up to rated voltage 660V AC 50/60HZ, rated current up to

Detailed

LC1-D series AC contactor is suitable for suing in the circuits up to rated voltage 660V AC 50/60HZ, rated current up to 95A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contactor, mechanical interlocking contactor, and star-delta starter. With the thermal relay, it is combined into the electromagnetic starter. The contactor is produced according to IEC947-2, VDE0660 & BS5452.

SPECIFICATION
Type LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32
Rated working current(A) AC3 9 12 18 25 32
AC4 3.5 5 7.7 8.5 12

AC3 capacity of phase 3 squirrel-cage motor AC3(KW)

220/230V 2.2 3 4 5.5 7.5
380/400V 4 5.5 7.5 11 15
415V 4 5.5 9 11 15
440V 4 5.5 9 11 15
500V 5.5 7.5 10 15 18.5
660/690V 5.5 7.5 10 15 18.5
Rated heat current (A) 20 20 32 40 50
Electrical life AC4?104 20 20-15 7-20 7-15 7-15
AC3?106 2 2 2 2 2
Mechanical life?106 20 20 20 20 20
Number of the contacts 3P+NO
3P+NC

OUTLINE & MOUNTING SIZES
Outline & mouting sizes of LC1-115-330 contactors are shown as followings:
A B C b1 P Q S Q1 M H L   Ga Ha
167 163 172 137 37 70 20 60 147 124 107 M6 80 110
167 171 172 137 40 70 20 58 150 124 107 M8
171 174 183 137 40 71 20 60 154 127 114 M8
171 197 183 137 48 71 25 52 172 127 114 M10
204 203 215 145 48 87 25 67 178 147 141 M10 96
213 206 220 145 48 91 25 74 181 181 145 M10